Poultry house control simulator

PLC control logic from our Capstone I design (Table 3.5), driven by simulated sensor inputs

Simulation · not measured data
SENSORS
Ventilation fanOFF
Heating bulbOFF
Buzzer alarmOFF
PLC stateNormal

Simulated inputs

Scenarios

Drag a slider or type a value and the PLC reacts on the next scan. "Run house model" lets the readings change by themselves, so you can watch the full loop: limit crossed, output ON, value recovers, output OFF.

Trend

Modbus holding registers (PLC view)

RegisterMeaningValue

Link OK · last valid reply 0 s ago

Response log

    Run summary

    Control rules used in this simulation

    ConditionPLC actionHysteresis / note
    Temperature above the age-based high setpointFan ONOFF 1.0 °C below setpoint
    Temperature below the age-based low limitHeating bulb ONOFF 1.0 °C above limit
    RH above 70 %Fan ONOFF below 68 %
    NH₃ at or above 8 ppm (80 % of limit)Fan ON (assist)OFF below 7 ppm
    NH₃ at or above 10 ppm, or CO₂ above 3000 ppmFan ON + buzzer latchedCO₂ fan OFF below 2800 ppm
    Temperature 2 °C outside its range, or RH above 80 %Buzzer latchedCleared by operator reset when normal
    Sensor fault, or no valid Modbus reply for 5 sFan ON, heater OFF, buzzer ONFail-safe state

    Age setpoints are demo values built from Table 2.1 (Cobb guide [30]); 14–21 d uses the report's 30 °C example. The house model is a simple first-order model made only to exercise the logic. The NH₃ value stands for the calibrated MQ-137 index expressed as ppm.